- Date
- 08/13/2018
- W/O
- 718156
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00457
- PipeID
- P20853
- Time
- 3:08 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K5983
- Sewer Name
- 05 IMPERIAL HIGHWAY EXTENSION TRUNK
- City
- HAWTHRONE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- WO_718156_TV05334_AUG2018
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 12 in.
- Width
- 12 in.
- Upstream MH
- 05 2458
- Downstream MH
- 05 2457
- Dir. of Survey
- Downstream
- Length Surveyed
- 225.9 ft.
- Total Length
- 225.9 ft.
- Structural Index
- 3
- Structural Quick
- 3B00
- Structural Rating
- 42
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 42
Pipe schematic from manhole 05 2458 to 05 2457 Observation photos (3)

151.6 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

157.2 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

163.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start