Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2020, 10:24 AM
  • J 0063_J 0062A_1292020_023232.mp4

Date
01/29/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P26340
Time
2:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1342
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Capital Improvement Program Assesment
Project
20200127MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0063
Downstream MH
J 0062A
Dir. of Survey
Downstream
Length Surveyed
540.8 ft.
Total Length
540.8 ft.
Structural Index
2
Structural Quick
3225
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole J 0063 to J 0062A
MH: J 0063MH: J 0062Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. MGO - General Observation - MAG COAT 98% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE UNDER MAG COAT26.4 ft. SSS - Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE26.4 ft. MGO - General Observation - 90% MAG COAT START36.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCREYTE194.4 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE299.2 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC461.5 ft. SSS - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING CONCRETE540.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE540.1 ft. MGO - General Observation - 90% MAG COAT FINISH540.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC540.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active540.8 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (9)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 98% START

    2 ft. - General Observation - MAG COAT 98% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE UNDER MAG COAT

  • Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    26.4 ft. - Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • General Observation - 90% MAG COAT START

    26.4 ft. - General Observation - 90% MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCREYTE

    36.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCREYTE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    194.4 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    299.2 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING CONCRETE

    461.5 ft. - Surface Spalling, from 08 to 11 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING CONCRETE

Observations (19)

DistanceCodeObservation
194.4SSSBLISTERING CONCRETE
2SAVSEVERE AGG SPORATIC
0MWM
0MWL
540.1SSSBLISTERING FLAKING CONCRETE
36.7SSSBLISTERING FLAKING CONCREYTE
540.1MGO90% MAG COAT FINISH
2MGOMAG COAT 98% START
0MGOConn. @ Mh, 9 O' Clock. Active
0AMH2:55AM
2SSSBLISTERING FLAKING CONCRETE UNDER MAG COAT
0MGOConn. @ Mh, 3 O' Clock. Active
540.1SAVSEVERE AGG SPORATIC
26.4SSSBLISTERING CONCRETE
26.4MGO90% MAG COAT START
461.5SSSBLISTERING FLAKING CONCRETE
540.1MGOConn. @ Mh, 3 O' Clock. Active
540.8AMH3:30AM
299.2SAVSEVERE AGG SPORATIC

Properties (6)

custom_field_three
SEVERE AGG SPORATIC-90% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2020-01-29T02:24:09-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false