Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2020, 11:47 AM
  • J 0069_J 0067_1282020_035311.mp4

Date
01/28/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P11648
Time
3:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1341
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Capital Improvement Program Assesment
Project
20200127MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0069
Downstream MH
J 0067
Dir. of Survey
Downstream
Length Surveyed
560.7 ft.
Total Length
560.7 ft.
Structural Index
2
Structural Quick
3325
Structural Rating
19
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
19
Pipe schematic from manhole J 0069 to J 0067
MH: J 0069MH: J 0067downstream0 ft. MGO - General Observation - MAG COAT 98% START0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:25AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE35.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE39.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE64.1 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE90.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open128.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC175.8 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE175.8 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG194.4 ft. SAV - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - XEVERE AGG SPORATIC335.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active560.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC560.1 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active560.1 ft. MGO - General Observation - 98% MAG COAT FINISH560.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE560.7 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (9)

  • General Observation - MAG COAT 98% START

    0 ft. - General Observation - MAG COAT 98% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

    35.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

    39.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    64.1 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    128.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

    175.8 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    175.8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - XEVERE AGG SPORATIC

    194.4 ft. - Surface Aggregate Visible, from 09 to 11 o'clock, within 8 inches of joint: NO - XEVERE AGG SPORATIC

Observations (20)

DistanceCodeObservation
560.1SAVSEVERE AGG SPORATIC
560.1MGOConn. @ Mh, 9 O' Clock. Active
560.1MGO98% MAG COAT FINISH
39.7SSSBLISTERING FLAKING CONCRETE
90.6TFOpen
0MGOMAG COAT 98% START
0MWM
128.7SAVSEVERE AGG SPORATIC
2SSSBLISTERING FLAKING CONCRETE
175.8SSSBLISTERING FLAKING CONCRETE
0MWL
0AMH4:25AM
35.6SSSBLISTERING FLAKING CONCRETE
175.8SAVSEVERE AGG
64.1SSSBLISTERING CONCRETE
560.7AMH5:10AM
194.4SAVXEVERE AGG SPORATIC
335.8TFAActive
0MGOConn. @ Mh, 9 O' Clock. Active
560.1SSSBLISTERING FLAKING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG VISIBLE-98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2020-01-28T03:47:52-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false