Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2020, 10:00 AM
  • J 0071_J OO69_1282020_021334.mp4

Date
01/28/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P11650
Time
2:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1341
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Capital Improvement Program Assesment
Project
20200127MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0071
Downstream MH
J OO69
Dir. of Survey
Downstream
Length Surveyed
461.8 ft.
Total Length
461.8 ft.
Structural Index
2
Structural Quick
3322
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole J 0071 to J OO69
MH: J 0071MH: J OO69downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. MGO - General Observation - MAG COAT 98% START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE87.9 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG207.6 ft. SRI - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MG COAT250.6 ft. SAV - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG333.3 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE340.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active461.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active461.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC461.3 ft. MGO - General Observation - MAG COAT 98% FINISH461.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING CONCRETE461.8 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 98% START

    2 ft. - General Observation - MAG COAT 98% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    87.9 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MG COAT

    207.6 ft. - Surface Roughness Increased, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE UNDER MG COAT

  • Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

    250.6 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    333.3 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

Observations (16)

DistanceCodeObservation
461.3MGOConn. @ Mh, 9 O' Clock. Active
340.8TFActive
207.6SRIBLISTERING CONCRETE UNDER MG COAT
0MWM
2SAVSEVERE AGG SPORATIC
87.9SAVSEVERE AGG
461.8AMH2:35AM
461.3SAVSEVERE AGG SPORATIC
461.3MGOMAG COAT 98% FINISH
333.3SSSBLISTERING PEELING CONCRETE
2MGOMAG COAT 98% START
461.3SSSBLISTERING FLAKING CONCRETE
250.6SAVSEVERE AGG
2SSSBLISTERING FLAKING CONCRETE
0AMH2:10AM
0MWL

Properties (6)

custom_field_three
SEVERE AGG VISIBLE- 98% MAG COAT
custom_field_two
3
customer
LACSD
datetime
2020-01-28T02:00:45-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false