Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2020, 12:21 PM
  • J 0074_J 0073_1272020_042123.mp4

Date
01/27/2020
W/O
0808084
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00063
PipeID
P11653
Time
4:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1340
Sewer Name
J JOINT OUTFALL J - UNIT 2D
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
31
Purpose
Capital Improvement Program Assesment
Project
20200127MDM_JOINT_OUTFALL_J_UNIT_2D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
J 0073
Downstream MH
J 0074
Dir. of Survey
Upstream
Length Surveyed
4.5 ft.
Total Length
4.5 ft.
Structural Index
4
Structural Quick
5141
Structural Rating
14
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
19
Pipe schematic from manhole J 0073 to J 0074
MH: J 0073MH: J 0074upstream0 ft. MSA - Survey Abandoned - UPLEG DOWNSTREAM SIPHON0.5 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG0.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR2.5 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG2.5 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE4.5 ft. MWL - Water Level, 50 %of cross sectional area4.5 ft. MWM - Water Mark, 80 %of cross sectional area4.5 ft. AMH - Downstream Manhole, Survey Begins - 4:25AM

Observation photos (5)

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

    4 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Survey Abandoned - UPLEG DOWNSTREAM SIPHON

    4.5 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON

Observations (8)

DistanceCodeObservation
4SAMSEVERE AGG
0MWL
0MWM
0AMH4:25AM
2SAPSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
4SRVCIRCUM REBAR
4.5MSAUPLEG DOWNSTREAM SIPHON

Properties (7)

additional_info
UPLEG DOWNSTREAM SIPHON
custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2020-01-27T04:21:00-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false