Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2020, 09:24 AM
  • 15 0775_15 0774_1242020_012919.mp4

Date
01/24/2020
W/O
0808481
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12976
Time
1:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1338R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20200123MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0774
Downstream MH
15 0775
Dir. of Survey
Upstream
Length Surveyed
385.9 ft.
Total Length
385.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3222
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0774 to 15 0775
MH: 15 0774MH: 15 0775upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:45AM0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN39.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped42.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped112.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open117.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped194.1 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open 70% ROOTS199.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active235.8 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 5 %, within 8 inches of joint: YESR238.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped242.8 ft. RMC - Roots Medium Connection, from 12 to 04 o'clock, 5 %, within 8 inches of joint: YES242.8 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open 100% ROOTS250.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 4%288.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped290.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open 100% ROOTS385.9 ft. MWL - Water Level, 10 %of cross sectional area385.9 ft. AMH - Downstream Manhole, Survey Begins - 1:25AM385.9 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (1)

  • Roots Medium Connection, from 12 to 04 o'clock, 5 %, within 8 inches of joint: YES

    143.1 ft. - Roots Medium Connection, from 12 to 04 o'clock, 5 %, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
191.8TFDOpen 70% ROOTS
268TFCCapped
135RFJ4%
346.8TFCCapped
95.1TFOpen 100% ROOTS
143.1RMC
97.4TFCCapped
0MWL
150.1RMJ
0AMH1:25AM
385.4MGOConn. @ Mh, 9 O' Clock. OPEN
0MWM
273.7TBOpen
147TFCCapped
143.1TFDOpen 100% ROOTS
385.9AMH1:45AM
186.3TFActive
343.6TFCCapped

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-01-24T01:24:09-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false