Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2020, 12:30 PM
  • 15 0776_15 0775_1232020_043842.mp4

Date
01/23/2020
W/O
0808481
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12977
Time
4:30 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1338R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20200123MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0776
Downstream MH
15 0775
Dir. of Survey
Downstream
Length Surveyed
399.3 ft.
Total Length
399.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0776 to 15 0775
MH: 15 0776MH: 15 0775downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:50AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area90.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active95.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open98.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Capped98.4 ft. RTJ - Roots Tap Joint, from 04 to 06 o'clock, 5 %, within 8 inches of joint: YESR119.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped122.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Capped143 ft. MGP - General Photograph - TAP ROOT143 ft. RTJ - Roots Tap Joint, from 12 to 02 o'clock, 10 %, within 8 inches of joint: YESR144.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-95% ROOTS147.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open168.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open217.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open232.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open98% ROOTS235.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open244.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - CAPPED250.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open317.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open399.3 ft. AMH - Downstream Manhole, Survey Ends - 5:15AM

Observation photos (2)

  • General Photograph - TAP ROOT

    143 ft. - General Photograph - TAP ROOT

  • Roots Tap Joint, from 12 to 02 o'clock, 10 %, within 8 inches of joint: YESR

    143 ft. - Roots Tap Joint, from 12 to 02 o'clock, 10 %, within 8 inches of joint: YESR

Observations (22)

DistanceCodeObservation
98.4TFCCapped
95.4TFOpen
119.9TFCCapped
0AMH4:50AM
217.3TFOpen
147.1TFOpen
244.2TFCCAPPED
143MGPTAP ROOT
168.3TFOpen
98.4RTJ
0MWM
235.3TFOpen
232.3TFDOpen98% ROOTS
90.4TFActive
144.1TFDOpen-95% ROOTS
0MGOConn. @ Mh, 3 O' Clock. Active
399.3AMH5:15AM
317.1TFOpen
122.3TFCCapped
0MWL
143RTJ
250.9TFOpen

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2020-01-23T04:30:39-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false