- Date
- 01/22/2020
- W/O
- 0808176
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00691
- PipeID
- P14306
- Time
- 12:28 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1334
- Sewer Name
- 18 NORTH PLANT OUTFALL TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 20
- Purpose
- Capital Improvement Program Assesment
- Project
- 20200122MDM_NORTH_PLANT_OUTFALL_TRUNK
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- 18 0454
- Downstream MH
- 18 0036
- Dir. of Survey
- Downstream
- Length Surveyed
- 101.6 ft.
- Total Length
- 101.6 ft.
- Structural Index
- 2
- Structural Quick
- 352A
- Structural Rating
- 37
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 41
Pipe schematic from manhole 18 0454 to 18 0036 Observation photos (4)

63.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

74.4 ft. - General Photograph - LONG SLIGHT 12:00

81.6 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT

101 ft. - General Observation - STOPLOG IN PLACE DOWNSTREAM