Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 27, 2019, 07:58 AM
  • D 0119_D 0118 _12272019_001302.mp4

Date
12/26/2019
W/O
803087
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10028
Time
11:58 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7221
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
MANHATTAN BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_803087_TV05172_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
D 0119
Downstream MH
D 0118
Dir. of Survey
Downstream
Length Surveyed
376.3 ft.
Total Length
376.3 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole D 0119 to D 0118
MH: D 0119MH: D 0118downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01194.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start141.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start370.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish375.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK376.3 ft. AMH - Downstream Manhole, Survey Ends - D 0118

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    141.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
370.7SRV
0MWL
0MWM
376.3MGOCONNECTION AT MH 3 O'CLOCK
0AMHD 0119
141.8SRV
376.3AMHD 0118
4.2SAP
375.2SAP

Properties (6)

additional_info
SC398513
custom_field_two
2
customer
LACSD
datetime
2019-12-26T23:58:09-08:00
documentation
PROPIPE
is_lateral_inspection
false