Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2019, 09:54 AM
  • D 0103_D 0102 _12302019_021147.mp4

Date
12/30/2019
W/O
803087
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10009
Time
1:54 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7222
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_803087_TV05172_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
D 0103
Downstream MH
D 0102
Dir. of Survey
Downstream
Length Surveyed
536 ft.
Total Length
536 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole D 0103 to D 0102
MH: D 0103MH: D 0102downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01030 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK4.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start4.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start536 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish536 ft. AMH - Downstream Manhole, Survey Ends - D 0102536 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
4.3SRV
536SRV
0.1MGOCONNECTION AT MH 9 O'CLOCK
0MWL
4.3SAP
536AMHD 0102
536SAP
0AMHD 0103
0MWM

Properties (6)

additional_info
SC398514
custom_field_two
2
customer
LACSD
datetime
2019-12-30T01:54:03-08:00
documentation
PROPIPE
is_lateral_inspection
false