Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 20, 2019, 11:20 AM
  • B 0703_B 0702 _12202019_033424.mp4

Date
12/20/2019
W/O
803092
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00110
PipeID
P09376
Time
3:20 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7257
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_803092_TV22155_DEC2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0703
Downstream MH
B 0702
Dir. of Survey
Downstream
Length Surveyed
265.5 ft.
Total Length
265.5 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2I12
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
262
Pipe schematic from manhole B 0703 to B 0702
MH: B 0703MH: B 0702downstream0 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - B 07032 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.3 ft. MGO - General Observation - 60% MAG COATING THROUGHOUT42 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN78.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN87.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN168.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN228.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN246.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN263.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish263.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish265.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE265.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE265.5 ft. AMH - Downstream Manhole, Survey Ends - B 0702

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    265.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
0VC@ MH
2SAV
78.4TFOPEN
265.5MGOCOCKROACHES IN MANHOLE
0MWL
16.3MGO60% MAG COATING THROUGHOUT
263.2DAGS
228.9TFOPEN
0MWM
2VC@ MH
2DAGS
87.6TFOPEN
42TFOPEN
265.5MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
168.6TFOPEN
265.5AMHB 0702
246.8TFOPEN
263.2SAV
0AMHB 0703

Properties (6)

additional_info
SC378891
custom_field_two
3
customer
LACSD
datetime
2019-12-20T03:20:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false