Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2020, 08:29 AM
  • B 1511_B 1510 _01092020_003507.mp4

Date
01/09/2020
W/O
802972
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01124
PipeID
P25626
Time
12:29 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7268
Sewer Name
B JOINT OUTFALL B - UNIT 6G
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_802972_TV16038_DEC2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 1511
Downstream MH
B 1510
Dir. of Survey
Downstream
Length Surveyed
23.6 ft.
Total Length
23.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4124
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole B 1511 to B 1510
MH: B 1511MH: B 1510downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 15110 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish23.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK23.6 ft. AMH - Downstream Manhole, Survey Ends - B 1510

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2DAGS
0MWL
23.6DAGS
23.6MGOCONNECTION AT MH 9 O'CLOCK
23.6AMHB 1510
0AMHB 1511
0MWM

Properties (7)

additional_info
SC398753
custom_field_two
3
customer
LACSD
datetime
2020-01-09T00:29:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
38891