Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2020, 11:43 AM
  • 18 0979 E_18 0978 _01102020_034626.mp4

Date
01/10/2020
W/O
803130
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00717
PipeID
P14830
Time
3:43 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7271
Sewer Name
18 WORSHAM CREEK RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
11
Purpose
Routine Assessment
Project
WO_803130_TV18061_DEC2019
Sewer Type
Siphon
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
18 0979 E
Downstream MH
18 0978
Dir. of Survey
Downstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 18 0979 E to 18 0978
MH: 18 0979 EMH: 18 0978downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0979, EAST SIPHON,.0 ft. MGO - General Observation - EAST BARREL HAS STOP LOG.2 ft. MSA - Survey Abandoned - VIEW OF DOWNLEG OF U/S EAST SIPHON.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES

Observation photos (2)

  • Survey Abandoned - VIEW OF DOWNLEG OF U/S EAST SIPHON.

    2 ft. - Survey Abandoned - VIEW OF DOWNLEG OF U/S EAST SIPHON.

  • Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
2MSAVIEW OF DOWNLEG OF U/S EAST SIPHON.
0MWL
0AMH18 0979, EAST SIPHON,.
2DAGS
0MGOEAST BARREL HAS STOP LOG.

Properties (6)

additional_info
SC398756
custom_field_two
4
customer
LACSD
datetime
2020-01-10T03:43:01-08:00
documentation
PRO PIPE
is_lateral_inspection
false