Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 17, 2020, 08:20 AM
  • 18 0490_18 0489_1172020_003638.mp4

Date
01/17/2020
W/O
0808176
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14344
Time
12:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1331
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20200117_NORTH_PLANT_OUTFALL_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Upstream MH
18 0490
Downstream MH
18 0489
Dir. of Survey
Downstream
Length Surveyed
99.9 ft.
Total Length
99.9 ft.
Structural Index
2
Structural Quick
352A
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
37
Pipe schematic from manhole 18 0490 to 18 0489
MH: 18 0490MH: 18 0489downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:35AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE22.6 ft. MGO - General Observation - SLIGHT OFFSET JOINT SEALED29.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H29.9 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H43.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H48.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H50.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL50.4 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - H63.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL66 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H70.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H76.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H80.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H86.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H86.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - H89 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H94.2 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H96.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL99.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN99.9 ft. AMH - Downstream Manhole, Survey Ends - 12:55AM

Observation photos (3)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H

    48.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

    80.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - H

Observations (24)

DistanceCodeObservation
29.9FLH
48.6FLH
99.3MGOConn. @ Mh, 3 O' Clock. OPEN
96.3FCSL
89FCH
50.4FCSL
8FCHAIRLINE
29.9FLH
0AMH12:35AM
43.3FCH
0MWM
86.4FCH
63.4FCSL
50.4FCH
76.2FCH
70.3FLH
94.2FCH
0MWL
2FLSLIGHT
99.9AMH12:55AM
86.4FLH
22.6MGOSLIGHT OFFSET JOINT SEALED
66FCH
80.9FLH

Properties (6)

custom_field_three
LONG SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2020-01-17T00:20:07-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false