Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 8, 2020, 08:30 AM
  • 02 2101_02 2100_182020_005249.mp4

Date
01/08/2020
W/O
0808077
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00283
PipeID
P04202
Time
12:30 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1322
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
20200107MDM_MONTEBELLO_INTERCEPTOR_TRUNK_SECTS_1_2
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 2101
Downstream MH
02 2100
Dir. of Survey
Downstream
Length Surveyed
475.9 ft.
Total Length
475.9 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 2101 to 02 2100
MH: 02 2101MH: 02 2100downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC12.9 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG71.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE93.6 ft. MGO - General Observation - 20% OLD MAG COAT START449.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open475.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE475.4 ft. MGO - General Observation - DOWNLEG UPSTREAM SIPHON475.4 ft. MGO - General Observation - 20% OLD MAG COAT475.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG475.9 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG

    12.9 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    71.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • General Observation - 20% OLD MAG COAT START

    93.6 ft. - General Observation - 20% OLD MAG COAT START

  • General Observation - DOWNLEG UPSTREAM SIPHON

    475.4 ft. - General Observation - DOWNLEG UPSTREAM SIPHON

Observations (14)

DistanceCodeObservation
475.4SSSBLISTERING PEELING CONCRETE
475.4MGODOWNLEG UPSTREAM SIPHON
12.9SAVSEVERE AGG
2SSSBLISTERING PEELING CONCRETE
475.4MGO20% OLD MAG COAT
71.6SSSPEELING CONCRETE
475.9AMH1:15AM
0MWM
449.5TFOpen
93.6MGO20% OLD MAG COAT START
2SAVSEVERE AGG SPORATIC
475.4SAVSEVERE AGG
0MWL
0AMH12:45AM

Properties (6)

custom_field_three
SEVERE AGG VISIBLE SPORATIC
custom_field_two
3
customer
LACSD
datetime
2020-01-08T00:30:14-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false