Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2020, 10:48 AM
  • 02 2103_02 2102_172020_025117.mp4

Date
01/07/2020
W/O
0808077
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00283
PipeID
P04204
Time
2:48 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
2H1322
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
20200107MDM_MONTEBELLO_INTERCEPTOR_TRUNK_SECTS_1_2
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 2103
Downstream MH
02 2102
Dir. of Survey
Downstream
Length Surveyed
452.8 ft.
Total Length
452.8 ft.
Structural Index
3
Structural Quick
3422
Structural Rating
16
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 2103 to 02 2102
MH: 02 2103MH: 02 2102downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:05AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE17.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC37.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC37.4 ft. MWL - Water Level, 10 %of cross sectional area37.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE37.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE37.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC37.4 ft. MWM - Water Mark, 30 %of cross sectional area215.2 ft. SAV - Surface Aggregate Visible, from 10 to 01 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC290.4 ft. MGO - General Observation - MAG COAT 10% START310.2 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - ROCK324.9 ft. SAV - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC452.3 ft. MGO - General Observation - MAG COAT 10% FINISH452.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE452.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC AT JOINTS452.8 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (3)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    17.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Observation - MAG COAT 10% START

    290.4 ft. - General Observation - MAG COAT 10% START

  • Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

    324.9 ft. - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG SPORATIC

Observations (19)

DistanceCodeObservation
310.2DSZROCK
37.4SAVSEVERE AGG SPORATIC
37.4MWL
290.4MGOMAG COAT 10% START
0MWM
17.1SAVSEVERE AGG SPORATIC
37.4SSSBLISTERING PEELING CONCRETE
215.2SAVSEVERE AGG SPORATIC
452.3MGOMAG COAT 10% FINISH
0AMH3:05AM
37.4SSSBLISTERING PEELING CONCRETE
452.3SSSBLISTERING PEELING CONCRETE
452.8AMH3:30AM
37.4SAVSEVERE AGG SPORATIC
452.3SAVSEVERE AGG SPORATIC AT JOINTS
2SSSBLISTERING PEELING CONCRETE
324.9SAVSEVERE AGG SPORATIC
0MWL
37.4MWM

Properties (6)

custom_field_three
SEVERE AGG SPORATIC
custom_field_two
3
customer
LACSD
datetime
2020-01-07T02:48:48-08:00
documentation
MARTIN,OLIVER 111,IGNACIO
is_lateral_inspection
false