Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2020, 09:21 AM
  • A 0020_B 0929_1162020_020501.mp4

Date
01/16/2020
W/O
080305
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00333
PipeID
P20071
Time
1:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1329
Sewer Name
A JOINT OUTFALL A - UNIT 3B
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
2020016MDM_JOINT_OUTFALL_A_UNIT_3B
Material
RCP-CTL
Shape
Square
Height
114 in.
Width
114 in.
Upstream MH
A 0020
Downstream MH
B 0929
Dir. of Survey
Downstream
Length Surveyed
639.8 ft.
Total Length
639.8 ft.
Structural Index
5
Structural Quick
5241
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
14
Pipe schematic from manhole A 0020 to B 0929
MH: A 0020MH: B 0929downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:05AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area1 ft. MGO - General Observation - LOOSE LINER IN MH2 ft. MGO - General Observation - 95% OLD MAG COAT START22.7 ft. MGO - General Observation - TILES 100% IN PLACE UNDER OLD MAG COAT62.4 ft. MGO - General Observation - POSSIBLE 25% MISSING TILES UNDER MAG COAT327.3 ft. MGO - General Observation - MISSING TILES UNDER MAG COAT556.6 ft. MGO - General Observation - MISSING TILES UNDER MAG COAT556.6 ft. SAM - Surface Aggregate Missing, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG AREAS OF MISSING TILES564.6 ft. MGO - General Observation - 95% OLD MAG COAT571.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - POSSIBLE UNDER MAG COAT585.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR POSSIBLE UNDER MAG COAT611.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT631.8 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR UNDER MAG COAT639.2 ft. MGO - General Observation - 95% OLD MAG COAT FINISH639.8 ft. AMH - Downstream Manhole, Survey Ends - 3:00AM

Observation photos (9)

  • General Observation - 95% OLD MAG COAT START

    2 ft. - General Observation - 95% OLD MAG COAT START

  • General Observation - TILES 100% IN PLACE UNDER OLD MAG COAT

    22.7 ft. - General Observation - TILES 100% IN PLACE UNDER OLD MAG COAT

  • General Observation - POSSIBLE 25% MISSING TILES UNDER MAG COAT

    62.4 ft. - General Observation - POSSIBLE 25% MISSING TILES UNDER MAG COAT

  • General Observation - MISSING TILES UNDER MAG COAT

    327.3 ft. - General Observation - MISSING TILES UNDER MAG COAT

  • General Observation - MISSING TILES  UNDER MAG COAT

    556.6 ft. - General Observation - MISSING TILES UNDER MAG COAT

  • Surface Aggregate Missing, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG AREAS OF MISSING TILES

    556.6 ft. - Surface Aggregate Missing, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - 95% OLD MAG COAT

    564.6 ft. - General Observation - 95% OLD MAG COAT

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - POSSIBLE UNDER MAG COAT

    571.8 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - POSSIBLE UNDER MAG COAT

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

    611.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

Observations (17)

DistanceCodeObservation
556.6MGOMISSING TILES UNDER MAG COAT
585.7SRVCIRCUM REBAR POSSIBLE UNDER MAG COAT
631.8SRVCIRCUM REBAR UNDER MAG COAT
327.3MGOMISSING TILES UNDER MAG COAT
564.6MGO95% OLD MAG COAT
639.8AMH3:00AM
62.4MGOPOSSIBLE 25% MISSING TILES UNDER MAG COAT
0AMH2:05AM
611.5SRVCIRCUM REBAR UNDER MAG COAT
22.7MGOTILES 100% IN PLACE UNDER OLD MAG COAT
1MGOLOOSE LINER IN MH
0MWL
556.6SAMSEVERE AGG AREAS OF MISSING TILES
639.2MGO95% OLD MAG COAT FINISH
2MGO95% OLD MAG COAT START
0MWM
571.8SRVPOSSIBLE UNDER MAG COAT

Properties (6)

custom_field_three
95% OLD MAG COAT,CIRCUM REBAR VISIBLE,MISSING TILE
custom_field_two
1
customer
LACSD
datetime
2020-01-16T01:21:18-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false