Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2019, 08:11 AM
  • 22 0441_22 0440 _12182019_002936.mp4

Date
12/18/2019
W/O
803095
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00815
PipeID
P16778
Time
12:11 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7214
Sewer Name
22 LARK ELLEN TRUNK, SECTS 2&3
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_803095_TV22047_DEC2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0441
Downstream MH
22 0440
Dir. of Survey
Downstream
Length Surveyed
360.6 ft.
Total Length
360.6 ft.
Structural Index
3
Structural Quick
3M25
Structural Rating
226
O&M Index
2
O&M Quick
412M
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
374
Pipe schematic from manhole 22 0441 to 22 0440
MH: 22 0441MH: 22 0440downstream0 ft. MGO - General Observation - CONNS. @ MH, 3 & 9 O'CLK. - NO FLOW SEEN IN EITHER.0 ft. AMH - Upstream Manhole, Survey Begins - 22 04410 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start82.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN - NO FLOW SEEN @ THIS TIME86.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN - NO FLOW SEEN @ THIS TIME184.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"236.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"240 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"332.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"335.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"337 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start337 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6" - CRACK MULTIPLE - CAP360 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish360 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish360 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish360.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0440

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    337 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
360.6AMH22 0440
0MGOCONNS. @ MH, 3 & 9 O'CLK. - NO FLOW SEEN IN EITHER.
332.6TFC
337SSS
360SSS
139.4TFOPEN - NO FLOW SEEN @ THIS TIME
335.1TBA
0AMH22 0441
0MWL
288.7TFC
337TFCCRACK MULTIPLE - CAP
86.6TFC
236.3TFC
360SAP
240TFC
360DAGS
184.1TFC
2DAGS
284.8TFC
0MWM
135.4TFC
2SAP
82.6TFOPEN - NO FLOW SEEN @ THIS TIME
188.4TFC

Properties (6)

additional_info
SC378888
custom_field_two
2
customer
LACSD
datetime
2019-12-18T00:11:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false