Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 31, 2019, 10:18 AM
  • 16 0514_16 0513 _12312019_023642.mp4

Date
12/31/2019
W/O
803099
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00659
PipeID
P13565
Time
2:18 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7260
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_803099_TV16119_DEC2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0514
Downstream MH
16 0513
Dir. of Survey
Downstream
Length Surveyed
279.7 ft.
Total Length
279.7 ft.
Structural Index
3
Structural Quick
3H2C
Structural Rating
171
O&M Index
2
O&M Quick
2J00
O&M Rating
110
Overall Index
2
Overall Quick
Overall Rating
281
Pipe schematic from manhole 16 0514 to 16 0513
MH: 16 0514MH: 16 0513downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 05140 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6" - IN U/S MH / STACK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"9.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start40.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"59.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start75.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish102.3 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"102.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start121.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"132.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish162.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"183.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"223.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start223.3 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"233.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish243.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"276.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish276.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE279.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0513

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    9.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    59.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    102.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    223.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    279.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (24)

DistanceCodeObservation
132.9CL
102.3TBA
3TBA
75.3CL
0AMH16 0514
2DAGS
233.8CL
0TBAIN U/S MH / STACK
279.7MGOCOCKROACHES IN MANHOLE
223.3CL
276.7DAGS
102.3CL
121.8TBA
162.9TBA
223.3TBA
0MWM
9.7CL
59.4CM
279.7AMH16 0513
183.2TBA
0MWL
243.3TBA
276.7CM
40.2TBA

Properties (6)

additional_info
SC378895
custom_field_two
2
customer
LACSD
datetime
2019-12-31T02:18:22-08:00
documentation
PRO PIPE
is_lateral_inspection
false