Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2019, 09:27 AM
  • 05 0356_05 2547 _11222019_013820.mp4

Date
11/22/2019
W/O
798212
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P24989
Time
1:27 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6339
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_798212_TV05012_NOV2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0356
Downstream MH
05 2547
Dir. of Survey
Downstream
Length Surveyed
289.5 ft.
Total Length
289.5 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
168
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
168
Pipe schematic from manhole 05 0356 to 05 2547
MH: 05 0356MH: 05 2547downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03562.8 ft. MGO - General Observation - mag coat2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start284.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289.5 ft. MGO - General Observation - ACTIVE CONNECTION @ D/S MH - 3 O'CLOCK289.5 ft. AMH - Downstream Manhole, Survey Ends - 05 2547

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.8MGOmag coat
289.5MGOACTIVE CONNECTION @ D/S MH - 3 O'CLOCK
0MWM
0MWL
0AMH05 0356
2.8SAV
284.6SAV
289.5AMH05 2547

Properties (6)

additional_info
SC365782
custom_field_two
3
customer
LACSD
datetime
2019-11-22T01:27:33-08:00
documentation
PROPIPE
is_lateral_inspection
false