Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2019, 10:31 AM
  • 05 0354_05 0353 _11252019_025044.mp4

Date
11/25/2019
W/O
798212
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05568
Time
2:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6340
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_798212_TV05012_NOV2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0354
Downstream MH
05 0353
Dir. of Survey
Downstream
Length Surveyed
431.1 ft.
Total Length
431.1 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
258
Pipe schematic from manhole 05 0354 to 05 0353
MH: 05 0354MH: 05 0353downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03542.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start430.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.1 ft. MGO - General Observation - ACTIVE CONNECTION AT D/S MH - 3 O'CLOCK431.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0353

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
0MWM
0AMH05 0354
2.1MGOMAG COAT
430.8SAV
2.1SAV
431.1MGOACTIVE CONNECTION AT D/S MH - 3 O'CLOCK
431.1AMH05 0353

Properties (6)

additional_info
SC365783
custom_field_two
3
customer
LACSD
datetime
2019-11-25T02:31:02-08:00
documentation
PROPIPE
is_lateral_inspection
false