Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 31, 2019, 10:16 AM
  • 18 0310_18 0309 _12312019_022825.mp4

Date
12/31/2019
W/O
803112
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00683
PipeID
P14142
Time
2:16 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7227
Sewer Name
18 LA MIRADA TRUNK, SECTS 1&2
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_803112_TV18145_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0310
Downstream MH
18 0309
Dir. of Survey
Downstream
Length Surveyed
277.5 ft.
Total Length
277.5 ft.
Structural Index
4
Structural Quick
5J3J
Structural Rating
440
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
440
Pipe schematic from manhole 18 0310 to 18 0309
MH: 18 0310MH: 18 0309downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03100.1 ft. MWM - Water Mark, 15 %of cross sectional area2.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start50.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"249 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0309277.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish277.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK277.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
277.5AMH18 0309
2.9SRV
249TF
0MGOCONNECTION AT MH 3 O'CLOCK
0.1MWM
0MWL
146.6TFC
0AMH18 0310
277.5SRV
50.2TF
277.5MGOCONNECTION AT MH 3 O'CLOCK
202.8TFC
2.9SAP
277.5SAP

Properties (6)

additional_info
SC398519
custom_field_two
2
customer
LACSD
datetime
2019-12-31T02:16:18-08:00
documentation
PROPIPE
is_lateral_inspection
false