Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 31, 2019, 11:22 AM
  • 18 0301_18 0300 _12312019_035501.mp4

Date
12/31/2019
W/O
803112
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00683
PipeID
P14132
Time
3:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7227
Sewer Name
18 LA MIRADA TRUNK, SECTS 1&2
City
LA MIRADA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_803112_TV18145_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0301
Downstream MH
18 0300
Dir. of Survey
Downstream
Length Surveyed
446.4 ft.
Total Length
446.4 ft.
Structural Index
4
Structural Quick
5L3Q
Structural Rating
599
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
599
Pipe schematic from manhole 18 0301 to 18 0300
MH: 18 0301MH: 18 0300downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 03010 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start30.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start135.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"232.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"288.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"336.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"345 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"384.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"393.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"425.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"431 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"443 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish443 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish446.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0300

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    107.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
336.7TFC
288.2TFC
107.5SRV
232.3TF
280.2TFC
345TFC
87.2TFC
30.9TFC
240.4TFC
431TF
443SAP
384.8TFC
183.5TF
135.7TFC
2.4SAP
0AMH18 0301
443SRV
0MWM
79.7TFC
446.4AMH18 0300
425.5TFC
0MWL
393.2TFC

Properties (6)

additional_info
SC398519
custom_field_two
2
customer
LACSD
datetime
2019-12-31T03:22:27-08:00
documentation
PROPIPE
is_lateral_inspection
false