Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2019, 09:22 AM
  • 02 0722_02 0721_12182019_013653.mp4

Date
12/18/2019
W/O
803134
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00294
PipeID
P03276
Time
1:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7216
Sewer Name
02 OLD RIVER SCHOOL ROAD TRUNK, SECTS 1&2
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_803134_TV02351_DEC2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0722
Downstream MH
02 0721
Dir. of Survey
Downstream
Length Surveyed
366 ft.
Total Length
366 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0722 to 02 0721
MH: 02 0722MH: 02 0721downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 07220 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area2.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start52.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start146.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"149.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"365.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366 ft. AMH - Downstream Manhole, Survey Ends - 02 0721366 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish366 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    20 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    132 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
266.5TF
365.9SSS
269.1TFC
366AMH02 0721
20FL
366FL
0AMH02 0722
149.3TFC
132CM
0MWL
0.1MWM
52.3TF
146.3TFC
54.8TFC
366CM
2.7SSS

Properties (6)

additional_info
SC398508
custom_field_two
2
customer
LACSD
datetime
2019-12-18T01:22:07-08:00
documentation
PROPIPE
is_lateral_inspection
false