Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 31, 2019, 10:41 AM
  • 18 0306A_18 0306 _12312019_024840.mp4

Date
12/31/2019
W/O
803058
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00683
PipeID
P14138
Time
2:41 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7228
Sewer Name
18 LA MIRADA TRUNK, SECTS 1&2
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_803058_TV18098_DEC2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0306A
Downstream MH
18 0306
Dir. of Survey
Downstream
Length Surveyed
110.5 ft.
Total Length
110.5 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0306A to 18 0306
MH: 18 0306AMH: 18 0306downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 0306A0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK - (POSSIBLY ACTIVE)0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start47.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish110.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish110.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0306

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMH18 0306A
95.5TFC
2.1SAP
110.4SAP
110.4SRV
0MGOCONNECTION AT MH 3 O'CLOCK - (POSSIBLY ACTIVE)
2.1SRV
47.2TFC
0MWM
0MWL
110.5AMH18 0306

Properties (6)

additional_info
SC398520
custom_field_two
2
customer
LACSD
datetime
2019-12-31T02:41:00-08:00
documentation
PROPIPE
is_lateral_inspection
false