Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2016, 09:20 AM
  • B 0399_B 0398_1282016_022954.mp4

  • B 0399_B 0398_1282016_022954.mp4

Date
01/28/2016
W/O
0547079
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00091
PipeID
P08911
Time
1:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
HOO34
Sewer Name
B JOINT OUTFALL B - UNIT 5A
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
07
Purpose
Routine Assessment
Project
20160128MDM_JOINT_OUTFALL_B_UNIT_5A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
B 0399
Downstream MH
B 0398
Dir. of Survey
Downstream
Length Surveyed
357.9 ft.
Total Length
357.9 ft.
Structural Index
3
Structural Quick
5231
Structural Rating
17
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
23
Pipe schematic from manhole B 0399 to B 0398
MH: B 0399MH: B 0398downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - MH CONN OPEN 3:000 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LAITACE COAT BLISTERING PEELING3.2 ft. MGP - General Photograph38.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open62.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"72.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - 90%GREASE OPEN92.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active111.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"115.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO127.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open127.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN 90% GREASE192.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open192.5 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG204.1 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG208.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - 90% GREASE305.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE SPORATIC357.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC357.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish357.7 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active357.9 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LAITACE COAT BLISTERING PEELING

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LAITACE COAT BLISTERING PEELING

  • General Photograph

    3.2 ft. - General Photograph

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

    115.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    192.5 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

    204.1 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE SPORATIC

    305.8 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE SPORATIC

Observations (23)

DistanceCodeObservation
0MWL
115.6SSS
2SSSLAITACE COAT BLISTERING PEELING
305.8SAVSEVERE SPORATIC
111.4TFC
357.7SAVSEVERE AGG SPORATIC
127.2TFOpen
192.5SRVSEVERE AGG
62.8TFC
38.6TFOpen
0MWM
357.9AMH2:45AM
0MGOMH CONN OPEN 3:00
204.1SRVSEVERE AGG
3.2MGP
357.7SSS
192.2TFOpen
72.7TFD90%GREASE OPEN
0AMH2:10AM
357.7MGOConn. @ Mh, 9 O' Clock. Active
92.4TFActive
127.3TFDOPEN 90% GREASE
208.5TFD90% GREASE

Properties (6)

custom_field_three
SEVERE AGG SPORATIC
custom_field_two
3
customer
LACSD
datetime
2016-01-28T01:20:28-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false