Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2016, 01:04 PM
Date
01/12/2016
W/O
0536420
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00362
PipeID
P05252
Time
5:04 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6669
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20160112MDM_JOINT_OUTFALL_C_UNIT_4D
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
A 0843
Downstream MH
C 0569
Dir. of Survey
Downstream
Length Surveyed
335.8 ft.
Total Length
335.8 ft.
Structural Index
3
Structural Quick
3422
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole A 0843 to C 0569
MH: A 0843MH: C 0569downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MGO - General Observation - LARGE STOPLOG TILTED BLOCKING MH BOTTOM30.9 ft. MGO - General Observation - SWOLLEN JOINT FILLER63.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE111.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - HAIRLINE139.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE171.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE175.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE211 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES335.6 ft. MGO - General Observation - SWOLLEN GASKET FILLER THROUGHOUT REACH335.8 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (4)

  • General Observation - LARGE STOPLOG TILTED BLOCKING MH BOTTOM

    0 ft. - General Observation - LARGE STOPLOG TILTED BLOCKING MH BOTTOM

  • General Observation - SWOLLEN JOINT FILLER

    30.9 ft. - General Observation - SWOLLEN JOINT FILLER

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE

    63.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE

  • General Observation - SWOLLEN GASKET FILLER THROUGHOUT REACH

    335.6 ft. - General Observation - SWOLLEN GASKET FILLER THROUGHOUT REACH

Observations (13)

DistanceCodeObservation
335.6MGOSWOLLEN GASKET FILLER THROUGHOUT REACH
139.7FLHAIRLINE
335.8AMH5:30AM
175.4FCHAIRLINE
211CL
30.9MGOSWOLLEN JOINT FILLER
111.6FLHAIRLINE
0MWM
0MWL
63.7FLHAIRLINE
171.5FLHAIRLINE
0AMH5:05AM
0MGOLARGE STOPLOG TILTED BLOCKING MH BOTTOM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2016-01-12T05:04:19-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false