Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 6, 2019, 07:51 AM
  • A 0416_A 0415 _12052019_235941.mp4

Date
12/05/2019
W/O
798107
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00322
PipeID
P08076
Time
11:51 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6354
Sewer Name
A JOA-1A LONG BEACH WRP SLUDGE GRAVITY SEWER
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_798107_TV19010_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
A 0416
Downstream MH
A 0415
Dir. of Survey
Downstream
Length Surveyed
117 ft.
Total Length
117 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0416 to A 0415
MH: A 0416MH: A 0415downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 04160 ft. MWL - Water Level, 35 %of cross sectional area6.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start6.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED115.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED116.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish116.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish117 ft. AMH - Downstream Manhole, Survey Ends - A 0415

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    6.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
6.9DAGS
6.9SSS
116.5SSS
0MWM
117AMHA 0415
115.9MGOCONNECTION AT MH 3 O'CLOCK CAPPED
115.9MGOCONNECTION AT MH 9 O'CLOCK CAPPED
0AMHA 0416
0MWL
116.5DAGS

Properties (6)

additional_info
SC365797
custom_field_two
3
customer
LACSD
datetime
2019-12-05T23:51:28-08:00
documentation
PROPIPE
is_lateral_inspection
false