Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2019, 08:17 PM
  • A 0403_A 0402 _12182019_122808.mp4

Date
12/18/2019
W/O
798107
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00322
PipeID
P08063
Time
12:17 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6835
Sewer Name
A JOA-1A LONG BEACH WRP SLUDGE GRAVITY SEWER
City
LONG BEACH
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_798107_TV19010_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
A 0403
Downstream MH
A 0402
Dir. of Survey
Downstream
Length Surveyed
338.4 ft.
Total Length
338.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
513L
O&M Rating
206
Overall Index
3
Overall Quick
Overall Rating
206
Pipe schematic from manhole A 0403 to A 0402
MH: A 0403MH: A 0402downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 75 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 04032 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start297.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 8"336.2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish338.4 ft. AMH - Downstream Manhole, Survey Ends - A 0402

Observation photos (1)

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
336.2DAGS
297.2TBA
338.4AMHA 0402
0MWL
0MWM
0AMHA 0403
2DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-12-18T12:17:05-08:00
documentation
PROPIPE
is_lateral_inspection
false