Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 5, 2019, 05:59 AM
  • 05 0524_05 2489 _12042019_221848.mp4

Date
12/04/2019
W/O
798297
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00462
PipeID
P20885
Time
9:59 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6351
Sewer Name
05 INGLEWOOD TRUNK #1 RELIEF
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_798297_TV05326_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0524
Downstream MH
05 2489
Dir. of Survey
Downstream
Length Surveyed
376.7 ft.
Total Length
376.7 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 05 0524 to 05 2489
MH: 05 0524MH: 05 2489downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - HEAVY STEAM0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 052425.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6"68.9 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES224.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES255.7 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Start266.1 ft. MWLS - Water Level, Sag in pipe, 15 %of cross sectional area, Finish315.9 ft. FC - Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES376.7 ft. AMH - Downstream Manhole, Survey Ends - 05 2489

Observation photos (4)

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    68.9 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    224.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Water Level, Sag in pipe, 15 %of cross sectional area, Start

    255.7 ft. - Water Level, Sag in pipe, 15 %of cross sectional area, Start

  • Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

    315.9 ft. - Fracture Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
0MWL
224.9CM
0MGOHEAVY STEAM
0MWM
266.1MWLS
25.7TF
0MGOCONNECTION AT MH 9 O'CLOCK
255.7MWLS
68.9FL
315.9FC
376.7AMH05 2489
0AMH05 0524

Properties (6)

additional_info
SC365794
custom_field_two
3
customer
LACSD
datetime
2019-12-04T21:59:02-08:00
documentation
PROPIPE
is_lateral_inspection
false