Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2019, 10:16 AM
  • 11_1_2_18122019_022240.mp4

Date
12/18/2019
W/O
0807676
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00282
PipeID
P03662
Time
2:16 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0302
Sewer Name
02 MONTEBELLO DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
20191216MDM_MONTEBELLO_DIVERSION_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 1088
Downstream MH
02 1087
Dir. of Survey
Downstream
Length Surveyed
334.8 ft.
Total Length
334.8 ft.
Structural Index
3
Structural Quick
553M
Structural Rating
361
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
361
Pipe schematic from manhole 02 1088 to 02 1087
MH: 02 1088MH: 02 1087downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC2 ft. MGO - General Observation - MH CONN 3:00 ACTIVE12.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC12.3 ft. MGO - General Observation - 20% OLD MAG COAT45.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB70.5 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR79.3 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR92 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR92 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR93.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB96.3 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR96.6 ft. MGP - General Photograph - CIRCUM REBAR99.9 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR142 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB158.7 ft. MGO - General Observation - RUST ON CONCRETE THROUGHOUT REACH232.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB239.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB293.4 ft. SAV - Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR296.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN334.1 ft. SSS - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE334.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE334.8 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (11)

  • Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    12.3 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - 20% OLD MAG COAT

    12.3 ft. - General Observation - 20% OLD MAG COAT

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    70.5 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

    92 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    92 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    96.3 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Photograph - CIRCUM REBAR

    96.6 ft. - General Photograph - CIRCUM REBAR

  • General Observation - RUST ON CONCRETE THROUGHOUT REACH

    158.7 ft. - General Observation - RUST ON CONCRETE THROUGHOUT REACH

  • Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    293.4 ft. - Surface Aggregate Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (26)

DistanceCodeObservation
99.9SRVCIRCUM REBAR
79.3SRVCIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
239.2TFCSTUB
0AMH2:20AM
0MWL
142TFCSTUB
92SRVLONG REBAR
0MWM
232.7TFCSTUB
293.4SAVCIRCUM REBAR
93.8TFCSTUB
12.3SAVSEVERE AGG SPORATIC
45.9TFCSTUB
12.3MGO20% OLD MAG COAT
96.6MGPCIRCUM REBAR
334.1SSSBLISTERING PEELING CONCRETE
2SAVSEVERE AGG SPORATIC
334.8AMH2:55AM
70.5SRVCIRCUM REBAR
2MGOMH CONN 3:00 ACTIVE
296.4TFOPEN
92SRVCIRCUM REBAR
158.7MGORUST ON CONCRETE THROUGHOUT REACH
96.3SRVCIRCUM REBAR
334.1SAVBLISTERING PEELING CONCRETE

Properties (6)

custom_field_three
LONG & CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2019-12-18T02:16:59-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection