Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2019, 09:52 AM
  • 7_1_2_17122019_020314.mp4

Date
12/17/2019
W/O
0807676
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00282
PipeID
P03665
Time
1:52 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0301
Sewer Name
02 MONTEBELLO DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
20191216MDM_MONTEBELLO_DIVERSION_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 1091
Downstream MH
02 1090
Dir. of Survey
Downstream
Length Surveyed
269.8 ft.
Total Length
269.8 ft.
Structural Index
3
Structural Quick
5342
Structural Rating
291
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
291
Pipe schematic from manhole 02 1091 to 02 1090
MH: 02 1091MH: 02 1090downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:05AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG9.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE9.9 ft. MGP - General Photograph - BLISTERING PEELING CONCRETE11.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC11.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG19 ft. SAV - Surface Aggregate Visible, from 01 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG44.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB50.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE92.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB95.7 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE96.8 ft. SRV - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIIRCUM REBAR POSSIBLE134.6 ft. MGO - General Observation - 20% MAG COAT150.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB179.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC197.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB246.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6" - STUB269.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC269.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE269.8 ft. AMH - Downstream Manhole, Survey Ends - 2:40AM

Observation photos (11)

  • Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Visible, from 03 to 04 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    9.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Photograph - BLISTERING PEELING CONCRETE

    9.9 ft. - General Photograph - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    11.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Visible, from 01 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG

    19 ft. - Surface Aggregate Visible, from 01 to 05 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    50.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

    95.7 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR POSSIBLE

  • Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIIRCUM REBAR POSSIBLE

    96.8 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIIRCUM REBAR POSSIBLE

  • General Observation - 20% MAG COAT

    134.6 ft. - General Observation - 20% MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    179.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

Observations (23)

DistanceCodeObservation
0MWL
0AMH2:05AM
246.8TFCSTUB
269.8AMH2:40AM
44.9TFCSTUB
0MWM
269.5SAVSEVERE AGG SPORATIC
9.9SSSBLISTERING PEELING CONCRETE
2SRVLONG & CIRCUM REBAR
50.4SSSPEELING CONCRETE
179.7SAVSEVERE AGG SPORATIC
95.7SRVCIRCUM REBAR POSSIBLE
19SAVSEVERE AGG
11.7SAVSEVERE AGG SPORATIC
11.7SAMSEVERE AGG
150.1TFCSTUB
197.8TFCSTUB
92.6TFCSTUB
269.5SSSBLISTERING PEELING CONCRETE
96.8SRVCIIRCUM REBAR POSSIBLE
9.9MGPBLISTERING PEELING CONCRETE
134.6MGO20% MAG COAT
2SAMSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG VISIBLE SPORATIC
custom_field_two
4
customer
LACSD
datetime
2019-12-17T01:52:07-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection