Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2019, 09:07 AM
  • 6_1_3_17122019_010752.mp4

Date
12/17/2019
W/O
0807676
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00282
PipeID
P03667
Time
1:07 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0300
Sewer Name
02 MONTEBELLO DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
20191216MDM_MONTEBELLO_DIVERSION_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 1092
Downstream MH
02 1093
Dir. of Survey
Upstream
Length Surveyed
191.9 ft.
Total Length
191.9 ft.
Structural Index
2
Structural Quick
3G2G
Structural Rating
194
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
194
Pipe schematic from manhole 02 1092 to 02 1093
MH: 02 1092MH: 02 1093upstream0 ft. AMH - Upstream Manhole, Survey Ends(COMPLETED BY REVERSE INSPECTION) - 1:30AM(COMPLETED BY REVERSE INSPECTION)0.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVER AGG SPORATIC45.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE166.5 ft. MGO - General Observation - 10% OLD MAG ON PIPE175.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE183.2 ft. MGP - General Photograph - 18" RCP189.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE189.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC191.9 ft. MWM - Water Mark, 20 %of cross sectional area191.9 ft. AMH - Downstream Manhole, Survey Begins - 1:10AM191.9 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (6)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • General Photograph - 18" RCP

    8.7 ft. - General Photograph - 18" RCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    16.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • General Observation - 10% OLD MAG ON PIPE

    25.4 ft. - General Observation - 10% OLD MAG ON PIPE

  • Upstream Manhole, Survey Ends(COMPLETED BY REVERSE INSPECTION) - 1:30AM(COMPLETED BY REVERSE INSPECTION)

    191.9 ft. - Upstream Manhole, Survey Ends(COMPLETED BY REVERSE INSPECTION) - 1:30AM(COMPLETED BY REVERSE INSPECTION)

Observations (12)

DistanceCodeObservation
8.7MGP18" RCP
0MWM
191.6SSSBLISTERING PEELING CONCRETE
191.9AMH1:30AM(COMPLETED BY REVERSE INSPECTION)
0AMH1:10AM
2SSSBLISTERING PEELING CONCRETE
25.4MGO10% OLD MAG ON PIPE
0MWL
2SAVSEVERE AGG SPORATIC
16.3SSSPEELING CONCRETE
191.6SAVSEVER AGG SPORATIC
146.5SSSPEELING CONCRETE

Properties (6)

custom_field_three
SEVERE AGG VISIBLE SPORATIC
custom_field_two
4
customer
LACSD
datetime
2019-12-17T01:07:10-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false