Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2019, 11:56 AM
  • 22 0433_H 1477_12112019_Manual.mp4

Date
12/11/2019
W/O
0803100
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00815
PipeID
P16770
Time
3:56 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0290
Sewer Name
22 LARK ELLEN TRUNK, SECTS 2&3
City
AZUA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
25
Purpose
Routine Assessment
Project
20191211MDM_LARK_ELLEN_TRUNK_SECTS_2_3
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
22 0433
Downstream MH
H 1477
Dir. of Survey
Downstream
Length Surveyed
279.8 ft.
Total Length
279.8 ft.
Structural Index
3
Structural Quick
4H3J
Structural Rating
455
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
455
Pipe schematic from manhole 22 0433 to H 1477
MH: 22 0433MH: H 1477downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 04330 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - FLAKING CONCRETE2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG47.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN49.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN53 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG111.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE138.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN196.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN244.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN279.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG279.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG279.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - FLAKING CONCRETE279.8 ft. AOC - Drop Connection, Survey Ends - 5:05AM

Observations (16)

DistanceCodeObservation
0MWM
0AMHMH 0433
2SSSFLAKING CONCRETE
244.6TFOPEN
279.2SAVSEVERE AGG
47.6TFOPEN
111.7TFAACTIVE
49.1TFOPEN
2SAVSEVERE AGG
0MWL
279.2SAMSEVERE AGG
279.2SSSFLAKING CONCRETE
53SAMSEVERE AGG
138.1TFOPEN
196.9TFOPEN
279.8AOC5:05AM

Properties (6)

custom_field_three
SEVERE AGG MISSING
custom_field_two
2
customer
LACSD
datetime
2019-12-11T03:56:14-08:00
documentation
MARTIN,OLIVER 111,IGNACIO
is_lateral_inspection
false