Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2015, 12:51 PM
  • VTS_04_1.mp4

Date
11/25/2015
W/O
0541729
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00682
PipeID
P14926
Time
4:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6652
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 5
City
LA HABRA HEIGHTS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20151124MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_3
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 1068
Downstream MH
18 1002
Dir. of Survey
Downstream
Length Surveyed
15.4 ft.
Total Length
15.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 18 1068 to 18 1002
MH: 18 1068MH: 18 1002downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. AMH - Upstream Manhole, Survey Begins - 5:40AM4.1 ft. MGP - General Photograph - 8" VCP6.2 ft. FC - Fracture Circumferential, from 09 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE15.2 ft. MGO - General Observation - MH CONN ACTIVE 3:0015.4 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (1)

  • General Photograph - 8" VCP

    4.1 ft. - General Photograph - 8" VCP

Observations (8)

DistanceCodeObservation
0MWM
0MWL
6.2FCHAIRLINE
4.1MGP8" VCP
15.2MGOMH CONN ACTIVE 3:00
15.4AMH5:45AM
0MGOMH CONN ACTIVE 3:00
0AMH5:40AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-11-25T04:51:34-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false