Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 24, 2015, 10:36 AM
  • VTS_01_1.mp4

Date
11/24/2015
W/O
0541776
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00680
PipeID
P14913
Time
2:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6652
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 3
City
LA HABRA HEIGHTS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20151124MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_3
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
18 1058
Downstream MH
18 1057
Dir. of Survey
Downstream
Length Surveyed
226.1 ft.
Total Length
226.1 ft.
Structural Index
2
Structural Quick
312A
Structural Rating
23
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
23
Pipe schematic from manhole 18 1058 to 18 1057
MH: 18 1058MH: 18 1057downstream0 ft. AMH - Upstream Manhole, Survey Begins - 3:35AM0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area50.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE58.3 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SLIGHT58.3 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE91.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT91.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT94.5 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SLIGHT101 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB152 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB153.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT170 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN186.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAIRLINE189.8 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE199.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB201.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SLIGHT216.5 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE222.2 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - HAIRLINE226.1 ft. AMH - Downstream Manhole, Survey Ends - 4:05AM

Observation photos (1)

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT

    91.4 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (21)

DistanceCodeObservation
58.3FCSLIGHT
226.1AMH4:05AM
0AMH3:35AM
186.8FCHAIRLINE
153.9FCSLIGHT
58.3FCHAIRLINE
189.8FCHAIRLINE
91.4FCSLIGHT
199.6TFCSTUB
222.2FCHAIRLINE
0MGOMH CONN ACTIVE 3:00
170TFOPEN
101TFCSTUB
216.5FCHAIRLINE
0MWM
0MWL
201.4FCSLIGHT
91.4FLSLIGHT
50.4TFACTIVE
94.5FCSLIGHT
152TFCSTUB

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2015-11-24T02:36:18-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection