Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2019, 09:27 AM
  • 02 1363_02 1362 _11252019_021014.mp4

Date
11/25/2019
W/O
798113
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00277
PipeID
P03886
Time
1:27 AM
Certificate
U-115-0622794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6828
Sewer Name
02 JANE STREET BRANCH TRUNK
City
E LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
RFIR_WO_798113_TV02343_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1363
Downstream MH
02 1362
Dir. of Survey
Downstream
Length Surveyed
271.9 ft.
Total Length
271.9 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
3
Overall Quick
Overall Rating
265
Pipe schematic from manhole 02 1363 to 02 1362
MH: 02 1363MH: 02 1362downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13630 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK2.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start63 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"99.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8", 8"120.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"165.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"192.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"240.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"269.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish269.4 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish271.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1362

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
269.4CM
99.4TF
0MWM
240.6TF
0MWL
0AMH02 1363
63TFC
165.6TF
5.1CM
192.4TF
2.5DAGS
269.4DAGS
271.9AMH02 1362
120.4TF
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-11-25T01:27:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false