Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 25, 2019, 11:59 AM
  • 02 1358_02 1357 _11252019_041714.mp4

Date
11/25/2019
W/O
798113
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00277
PipeID
P03881
Time
3:59 AM
Certificate
U-115-0622794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6828
Sewer Name
02 JANE STREET BRANCH TRUNK
City
E LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
RFIR_WO_798113_TV02343_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1358
Downstream MH
02 1357
Dir. of Survey
Downstream
Length Surveyed
357.3 ft.
Total Length
357.3 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
2
O&M Quick
2M00
O&M Rating
142
Overall Index
3
Overall Quick
Overall Rating
352
Pipe schematic from manhole 02 1358 to 02 1357
MH: 02 1358MH: 02 1357downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13583 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"77.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"84.2 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, #v, within 8 inches of joint: YES, 8", 1"169.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"172.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"272.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"275.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"354.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish357.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1357

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
84.2TBI
357.3AMH02 1357
169.1TFC
172.1TFC
354.1CM
275.5TF
0MWM
77.7TFC
77.2TF
4.2CM
0MWL
3DAGS
272.1TFC
0AMH02 1358
354.1DAGS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-11-25T03:59:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false