Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 11, 2019, 06:01 AM
  • 18 0616_18 0615 _10072019_232142.mp4

Date
07/10/2019
W/O
771943
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00692
PipeID
P14466
Time
11:01 PM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6756
Sewer Name
18 NORTH PLANT OUTFALL RELIEF TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_771943_TV18036_JUN2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 0616
Downstream MH
18 0615
Dir. of Survey
Downstream
Length Surveyed
27.7 ft.
Total Length
27.7 ft.
Structural Index
2
Structural Quick
4121
Structural Rating
7
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 18 0616 to 18 0615
MH: 18 0616MH: 18 0615downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06160 ft. MWL - Water Level, 5 %of cross sectional area0 ft. VC - Vermin Cockroach1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start10.8 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES17.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES24 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES25.7 ft. TFA - Tap Factory Made Active, at 06 o'clock, -, within 8 inches of joint: YES, 8" - DROP CONNECTION27.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish27.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Finish27.7 ft. AOC - Drop Connection, Survey Ends - 18 0615

Observation photos (5)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    10.8 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    17.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    24 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0MWM
0AMH18 0616
27.2DAGS
27.2DAE
10.8CC
0MWL
1DAE
17.2CL
25.7TFADROP CONNECTION
24FM
0VC
27.7AOC18 0615
1DAGS

Properties (6)

additional_info
SC378259
custom_field_two
3
customer
LACSD
datetime
2019-07-10T23:01:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false