Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2019, 09:05 AM
  • 1_1_2_12122019_012455.mp4

  • 1_1_2_12122019_012455.mp4

Date
12/12/2019
W/O
0798195
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00289
PipeID
P18810
Time
1:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0284
Sewer Name
02 MONTEREY PARK EXTENSION TRUNK
City
LOS ANGLES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20191212MDM_MONTERY_PARK_EXTENSION_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
02 1654
Downstream MH
02 1655
Dir. of Survey
Upstream
Length Surveyed
160.8 ft.
Total Length
160.8 ft.
Structural Index
3
Structural Quick
4E2E
Structural Rating
192
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
192
Pipe schematic from manhole 02 1654 to 02 1655
MH: 02 1654MH: 02 1655upstream0 ft. AMH - Upstream Manhole, Survey Ends - 1:45AM0.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED65.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN82 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED124.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED149 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED159 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG159 ft. MGO - General Observation - 15" NRCP160.8 ft. MGO - General Observation - MH CONN 9:00 ACTIVE160.8 ft. MWM - Water Mark, 30 %of cross sectional area160.8 ft. MWL - Water Level, 10 %of cross sectional area160.8 ft. AMH - Downstream Manhole, Survey Begins - 1:20AM

Observation photos (5)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    1.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 15" NRCP

    1.8 ft. - General Observation - 15" NRCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    11.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    36.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    78.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (13)

DistanceCodeObservation
160.3SAMSEVERE AGG
11.8SSSPEELING CONCRETE SEVERE AGG ATTACHED
78.8SSSPEELING CONCRETE SEVERE AGG ATTACHED
1.8SAMSEVERE AGG
160.8AMH1:45AM
0MGOMH CONN 9:00 ACTIVE
0MWM
1.8MGO15" NRCP
160.3SSSPEELING CONCRETE SEVERE AGG ATTACHED
36.1SSSPEELING CONCRETE SEVERE AGG ATTACHED
95.5TFOPEN
0MWL
0AMH1:20AM

Properties (7)

additional_info
REVERSE INSPECTION
custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2019-12-12T01:05:54-08:00
documentation
MARTIN,REVELES,OLIVER 111,IGNACIO
is_lateral_inspection
false