Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 23, 2019, 07:53 AM
  • 29 0555_29 0554 _23072019_011347.mp4

Date
07/23/2019
W/O
776901
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00537
PipeID
P24701
Time
12:53 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6719
Sewer Name
29 21ST STREET SEWER
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_776901_TV29107_JUL2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0555
Downstream MH
29 0554
Dir. of Survey
Downstream
Length Surveyed
306.9 ft.
Total Length
306.9 ft.
Structural Index
3
Structural Quick
4233
Structural Rating
17
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
17
Pipe schematic from manhole 29 0555 to 29 0554
MH: 29 0555MH: 29 0554downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 05550 ft. MWM - Water Mark, 10 %of cross sectional area10 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES52.8 ft. TFB - Tap Factory Made Abandoned, at 09 o'clock, -, within 8 inches of joint: NO, 6"59.7 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES67.2 ft. RPL - Repair Localized Liner, within 8 inches of joint: YES - CIPP86 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start102.4 ft. TFB - Tap Factory Made Abandoned, at 09 o'clock, -, within 8 inches of joint: NO, 6"154.9 ft. TFB - Tap Factory Made Abandoned, at 09 o'clock, -, within 8 inches of joint: NO, 6"201.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES230 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES256.7 ft. TFB - Tap Factory Made Abandoned, at 09 o'clock, -, within 8 inches of joint: NO, 6"299.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"303.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish306.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0554

Observation photos (5)

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    10 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    59.7 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    86 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    213.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    230 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0MWL
154.9TFB
230FM
59.7CM
52.8TFB
303.9TFC
10CM
0AMH29 0555
256.7TFB
204.4TF
213.7FM
0MWM
304.9CM
67.2RPLCIPP
299.3TBA
102.4TFB
306.9AMH29 0554
201.9TB
86CM

Properties (6)

additional_info
SC378218
custom_field_two
3
customer
LACSD
datetime
2019-07-23T00:53:11-07:00
documentation
PROPIPE
is_lateral_inspection
false