Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 9, 2019, 09:02 AM
  • 22 0566_22 0565B _09092019_022353.mp4

Date
09/09/2019
W/O
787674
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00791
PipeID
P16912
Time
2:02 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6957
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
WO_787674_TV22006_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0566
Downstream MH
22 0565B
Dir. of Survey
Downstream
Length Surveyed
276.3 ft.
Total Length
276.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 22 0566 to 22 0565B
MH: 22 0566MH: 22 0565Bdownstream0 ft. VC - Vermin Cockroach, within 8 inches of joint: YES0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH0 ft. AMH - Upstream Manhole, Survey Begins - 22 05662 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start57.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"62.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"113 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"148.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"199 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"204.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"273.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish273.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish276.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0565B276.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
62.5TFC
0VC
2SAP
276.3AMH22 0565B
0MWL
0MWM
148.8TFC
199TFC
0MGOCONNECTIONS AT BOTH 3 AND 9 O'CLOCK IN MH
273.9DAGS
0AMH22 0566
276.3MGOCONNECTION AT MH 9 O'CLOCK
57.1TFC
2DAGS
113TFC
273.9SAP
204.2TFC

Properties (6)

additional_info
SC378564
custom_field_two
3
customer
LACSD
datetime
2019-09-09T02:02:25-07:00
documentation
PRO PIPE
is_lateral_inspection
false