Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2019, 09:48 AM
  • 22 0559_22 0558 _09102019_030154.mp4

Date
09/10/2019
W/O
787674
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00791
PipeID
P16901
Time
2:48 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6817
Sewer Name
22 BEN LOMOND TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
WO_787674_TV22006_SEP2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0559
Downstream MH
22 0558
Dir. of Survey
Downstream
Length Surveyed
282.8 ft.
Total Length
282.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 22 0559 to 22 0558
MH: 22 0559MH: 22 0558downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05592 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT THROUGHOUT79 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"140 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"230.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"240.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"279.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish282.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0558282.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT THROUGHOUT

    2 ft. - General Observation - MAG COAT THROUGHOUT

Observations (13)

DistanceCodeObservation
230.7TF
282.8AMH22 0558
2SAV
0MWM
282.8MGOCONNECTION AT MH 3 O'CLOCK
0MWL
140TF
240.8TF
2MGOMAG COAT THROUGHOUT
109.5TF
279.5SAV
0AMH22 0559
79TF

Properties (6)

additional_info
SC378429
custom_field_two
3
customer
LACSD
datetime
2019-09-10T02:48:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false