Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2019, 06:06 AM
  • 30 0134_30 0133_12092019_221707.mp4

Date
12/09/2019
W/O
798601
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17839
Time
10:06 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7206
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_798601_TV30036_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
30 0134
Downstream MH
30 0133
Dir. of Survey
Downstream
Length Surveyed
171.3 ft.
Total Length
171.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 30 0134 to 30 0133
MH: 30 0134MH: 30 0133downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 013458.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"65 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.1 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES94 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"139.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"162.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK171.3 ft. AMH - Downstream Manhole, Survey Ends - 30 0133

Observation photos (2)

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    58.2 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    71.1 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
139.2TFC
162.5TFC
127.9TFC
171.3MGOCONNECTION AT MH 3 O'CLOCK
0MWM
153.9TFC
65TFC
171.3AMH30 0133
94TFC
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
58.2TB
0AMH30 0134
71.1RFJ

Properties (6)

additional_info
SC365799
custom_field_two
4
customer
LACSD
datetime
2019-12-09T22:06:15-08:00
documentation
PROPIPE
is_lateral_inspection
false