Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2019, 11:12 AM
  • 30 0143_30 0142 _12092019_031915.mp4

Date
12/09/2019
W/O
798601
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17848
Time
3:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7205
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
TORRANCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_798601_TV30036_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
30 0143
Downstream MH
30 0142
Dir. of Survey
Downstream
Length Surveyed
140.1 ft.
Total Length
140.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1300
O&M Rating
3
Overall Index
1
Overall Quick
Overall Rating
3
Pipe schematic from manhole 30 0143 to 30 0142
MH: 30 0143MH: 30 0142downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 01430 ft. MWM - Water Mark, 15 %of cross sectional area3.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"45.6 ft. RFJ - Roots Fine Joint, from 08 to 11 o'clock, within 8 inches of joint: YES60 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.2 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES109.9 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start117 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish140.1 ft. AMH - Downstream Manhole, Survey Ends - 30 0142

Observation photos (2)

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

    3.6 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    109.9 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
3.6TBA
0MGOCONNECTION AT MH 3 O'CLOCK
140.1AMH30 0142
104.2RFJ
0MWL
109.9RFJ
63.2TFC
117TFC
0AMH30 0143
140RFJ
0MWM
45.6RFJ
60TFC

Properties (6)

additional_info
SC365798
custom_field_two
4
customer
LACSD
datetime
2019-12-09T03:12:24-08:00
documentation
PROPIPE
is_lateral_inspection
false