Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2019, 11:20 AM
  • 30 0142_30 0141 _12092019_032751.mp4

Date
12/09/2019
W/O
798601
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17847
Time
3:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7205
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
TORRANCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_798601_TV30036_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
30 0142
Downstream MH
30 0141
Dir. of Survey
Downstream
Length Surveyed
142.6 ft.
Total Length
142.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4112
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 30 0142 to 30 0141
MH: 30 0142MH: 30 0141downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 01427.6 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start54 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"54 ft. RFL - Roots Fine Lateral, at 02 o'clock57.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.6 ft. RBL - Roots Ball Lateral, at 10 o'clock, 80 %62 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.6 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish142.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK142.6 ft. AMH - Downstream Manhole, Survey Ends - 30 0141

Observation photos (3)

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    54 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Roots Ball Lateral, at 10 o'clock, 80 %

    57.6 ft. - Roots Ball Lateral, at 10 o'clock, 80 %

Observations (12)

DistanceCodeObservation
62TFC
54TB
142.6RFJ
142.6MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MWM
7.6RFJ
57.4TF
142.6AMH30 0141
57.6RBL
0AMH30 0142
54RFL

Properties (6)

additional_info
SC365798
custom_field_two
4
customer
LACSD
datetime
2019-12-09T03:20:17-08:00
documentation
PROPIPE
is_lateral_inspection
false