Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2019, 11:56 AM
  • 30 0140_30 0139 _12102019_030120.mp4

Date
12/10/2019
W/O
798601
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17845
Time
3:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7206
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
WO_798601_TV30036_NOV2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
30 0140
Downstream MH
30 0139
Dir. of Survey
Downstream
Length Surveyed
197.3 ft.
Total Length
197.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3112
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 30 0140 to 30 0139
MH: 30 0140MH: 30 0139downstream0 ft. AMH - Upstream Manhole, Survey Begins - 30 01400 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area22.2 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start62.5 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 6"103.8 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish115.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.7 ft. RFL - Roots Fine Lateral, at 02 o'clock118.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.3 ft. AMH - Downstream Manhole, Survey Ends - 30 0139197.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    22.2 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 6"

    62.5 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 6"

Observations (11)

DistanceCodeObservation
0AMH30 0140
197.3AMH30 0139
0MWM
115.4TF
0MWL
103.8RFJ
197.3MGOCONNECTION AT MH 3 O'CLOCK
118.7RFL
62.5TBI
22.2RFJ
118.7TF

Properties (6)

additional_info
SC365799
custom_field_two
5
customer
LACSD
datetime
2019-12-10T03:56:47-08:00
documentation
PROPIPE
is_lateral_inspection
false