Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 12, 2019, 10:48 AM
  • B 0558_B 0557 _12122019_030518.mp4

Date
12/12/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09105
Time
2:48 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7151
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0557
Downstream MH
B 0558
Dir. of Survey
Upstream
Length Surveyed
351.1 ft.
Total Length
351.1 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
207
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
345
Pipe schematic from manhole B 0557 to B 0558
MH: B 0557MH: B 0558upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 05581.8 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish349.1 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start349.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start351.1 ft. MWL - Water Level, 5 %of cross sectional area351.1 ft. AMH - Downstream Manhole, Survey Begins - B 0557351.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE351.1 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (2)

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
2SCP
0AMHB 0557
0MGOCOCKROACHES IN MANHOLE
349.3SCP
2DAGS
0MWM
351.1AMHB 0558
349.3DAGS

Properties (6)

additional_info
SC378883
custom_field_two
2
customer
LACSD
datetime
2019-12-12T02:48:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false