Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2019, 06:36 AM
  • B 0568A_B 0568 _12092019_224154.mp4

Date
12/09/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09117
Time
10:36 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7146
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
26
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0568A
Downstream MH
B 0568
Dir. of Survey
Downstream
Length Surveyed
90.5 ft.
Total Length
90.5 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
51
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
3
Overall Quick
Overall Rating
85
Pipe schematic from manhole B 0568A to B 0568
MH: B 0568AMH: B 0568downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 0568A0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start88.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish88.5 ft. SCP - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish90.5 ft. AMH - Downstream Manhole, Survey Ends - B 056890.5 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK

Observation photos (2)

  • Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
88.5DAGS
90.5AMHB 0568
88.5SCP
90.5MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0MWL
0AMHB 0568A
2SCP
2DAGS
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC378878
custom_field_two
2
customer
LACSD
datetime
2019-12-09T22:36:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false