Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2019, 06:55 AM
  • B 0567_B 0566 _12092019_230201.mp4

Date
12/09/2019
W/O
798600
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09115
Time
10:55 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7146
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
26
Purpose
Routine Assessment
Project
WO_798600_TV15120_NOV2019
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
B 0567
Downstream MH
B 0566
Dir. of Survey
Downstream
Length Surveyed
128.9 ft.
Total Length
128.9 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
75
O&M Index
2
O&M Quick
2D00
O&M Rating
50
Overall Index
3
Overall Quick
Overall Rating
125
Pipe schematic from manhole B 0567 to B 0566
MH: B 0567MH: B 0566downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - B 05672 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start127.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish127.7 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish128.9 ft. AMH - Downstream Manhole, Survey Ends - B 0566128.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    128.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MWM
2DAGS
0MWL
127.7DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
128.9AMHB 0566
0MGOCOCKROACHES IN MANHOLE
128.9MGOCOCKROACHES IN MANHOLE
127.7SCP
2SCP
0AMHB 0567

Properties (6)

additional_info
SC378878
custom_field_two
2
customer
LACSD
datetime
2019-12-09T22:55:42-08:00
documentation
PRO PIPE
is_lateral_inspection
false